Minimum sockets and light points per room

In the US, the NEC asks for a receptacle so that no point along a wall is more than 6 ft (1.8 m) from one, which works out to one every 12 ft (3.7 m) of usable wall, plus a switched light in every habitable room. In Italy, CEI 64-8 level 1 sets a fixed count per room: 4 sockets and 1 light point for a room of 8 to 12 m², 5 and 1 from 12 to 20 m², 6 and 2 above 20 m², with separate figures for kitchens, bathrooms and corridors.

Updated October 3, 2026 · Cristiano Soleti

United States: NEC 210.52 and 210.70

The National Electrical Code (NFPA 70) does not give a count per room. It gives a spacing rule for receptacles along the walls and a list of places that need at least one, and it asks for a wall-switched lighting outlet in habitable rooms, bathrooms and hallways.

RoomSocketsLight pointsNote
Living room, bedroom, dining room, kitchen walls and similar rooms1 per 12 ft (3.7 m) of usable wall1, wall switched210.52(A): no point along the floor line more than 6 ft (1.8 m) from a receptacle. Wall spaces 2 ft (600 mm) or wider count
Bathroom1, within 3 ft (900 mm) of the basin1, wall switched210.52(D), with GFCI protection under 210.8
Laundry area11, wall switched210.52(F)
Hallway of 10 ft (3.0 m) or more11, wall switched210.52(H)
Balcony, deck or porch1Not counted here210.52(E)(3)

Italy: CEI 64-8, level 1

CEI 64-8 chapter 37 defines three levels for a home's electrical installation. Level 1 is the minimum for a new or fully rebuilt installation. The table gives the minimum socket points and light points per room.

RoomSocketsLight pointsNote
Living room, bedroom, study: 8 to 12 m²41A bedroom may have one socket fewer
Living room, bedroom, study: 12 to 20 m²51A bedroom may have one socket fewer
Living room, bedroom, study: over 20 m²62
Kitchen51Two of the sockets at worktop level
Kitchenette20Added to the room it opens onto; one at worktop level
Bathroom or shower room22One socket is enough without a washing machine
Separate WC11
Laundry31
Entrance11
Corridor up to 5 m11
Corridor over 5 m22
Balcony or terrace of 10 m² or more11Nothing required under 10 m²
Storage room of 1 m² or more01
Bedroom10.9 m²Living room28.1 m²Hallway3.2 m²Bathroom4.8 m²

Worked example: a 47 m² one-bedroom flat

The same flat, checked both ways by Layroom's editor. Each cell reads sockets placed over sockets needed, then lights placed over lights needed. The NEC figure depends on the length of usable wall, so it changes when a door or window moves.

RoomAreaCEI 64-8 level 1NEC
Bedroom10.9 m²2/3 · 1/12/3 · 1/1
Living room28.1 m²5/6 · 4/25/5 · 4/1
Hallway3.2 m²0/1 · 1/10/0 · 1/1
Bathroom4.8 m²1/2 · 1/21/1 · 1/1

What these numbers are not

  • They are minimum counts for planning a layout. They are not a design, a load calculation or a certificate of compliance.
  • The NEC is adopted state by state, in different editions and with local amendments. The authority having jurisdiction decides.
  • Kitchen countertop receptacles (NEC 210.52(C)), outdoor, garage and basement receptacles have their own rules and are not covered here.
  • CEI 64-8 levels 2 and 3 ask for more points per room; level 1 is the floor, not the target.

Sources

Questions

How many outlets does a bedroom need by code?
Under the NEC, enough that no point along a wall is more than 6 ft from a receptacle, so about one per 12 ft of usable wall: a 10 by 12 ft bedroom usually needs four. Under CEI 64-8 level 1 in Italy, a bedroom of 8 to 12 m² needs at least 3 sockets and one of 12 to 20 m² at least 4.
How far apart can receptacles be under the NEC?
At most 12 ft (3.7 m) apart along a wall, because NEC 210.52(A) requires that no point along the floor line of a wall space be more than 6 ft (1.8 m) from a receptacle. Any wall space 2 ft (600 mm) or wider counts.
How many sockets does a kitchen need under CEI 64-8?
At least 5 socket points and 1 light point at level 1, with two of the sockets at worktop level. A kitchenette that is part of another room adds 2 sockets to that room's count.
Does a bathroom need a GFCI outlet?
In the US, yes: NEC 210.52(D) requires at least one receptacle within 3 ft of the basin and 210.8 requires GFCI protection for bathroom receptacles. In Italy, CEI 64-8 level 1 asks for 2 sockets and 2 light points in a bathroom, or 1 socket if there is no washing machine.
Is there a tool that counts sockets and lights per room?
Yes. Layroom's free editor detects the rooms on a floor plan, counts the sockets and light points you place in each, and compares them with the NEC spacing rule or the CEI 64-8 level 1 table.